upper DEL-Notice: 658,79 € (date: 06.02.2012)

 

previous product

Control cables, twisted pairs

2-LiHCH TP, shielded, FRNC

installation
FRNC
halogen free

Application:

Measuring, signal-, and control-technology as as well as in EDP periphery, where safety regulations prescribe the use of halogen-free / flame-retardant cable. The pair twisting optimizes cross-talk attenuation and prevents electrical coupling within the line to a large extent.

Increased interference protection as well as increased mechanical maximum stress by copper braid.

Construction:

Conductor:

  • bare stranded copper wire

Structure of conductor:

  • 18 x 0,10mm

Core insulation:

  • no halogen material

Core code:

  • DIN 47100

First twisting:

  • conductors to pairs

Twisting:

  • pairs in layers

Shield:

  • tinned copper braid, approx. 85%

Jacket:

  • FRNC, grey sim. RAL 7001

Technical characteristics:

Insulation resistance:

  • min. 200 MOhm x km bei +20°C

Capacity:

  • approx. 65pF/m

Characteristic impedance:

  • approx. 100Ohm +/-10%

Operating voltage:

  • 350V

Testing voltage:

  • 800V

Ampacity:

  • 1,5A (at +25°C)

Temperature range:

  • static:       -25°C to +80°C
  • dynamic:    -5°C to +70°C

Bending radius:

  • min. 15x O.D.

Packaging:

rings at 100m, reels

Important product information

Important product information

- Flame retardant acc. to DIN VDE 0472 part 804 testing C / IEC 332.3
- zero halogen acc. to DIN VDE 0472 part 815 / IEC 754-1
- no acid gas emission acc. to DIN VDE 0472 part 813 / IEC 754-2
- low smoke emission in case of fire

Product range

2-LiHCH TP, shielded, FRNC

Order no.dimensionO.D.weightco.-weight
(qmm)(ca. mm)(kg/km)(kg/km)
4306014003x2x0,145,54726,1
4310014005x2x0,146,57637,3
4316014008x2x0,147,811053,7
43260140013x2x0,149,513569,0
43400140020x2x0,1411,0187110,0
43500140025x2x0,1412,0225127,4