Application / Description
For internal wiring in inhouse installations, in switching and distribution installations as well as protected installations in or on luminaires.
Product range
Order-No. | Cross section qmm | Structure of conductor mm | O.D. approx. mm | weight kg/km | Cu-weigth kg/km |
---|---|---|---|---|---|
6610150 | 1,50 | 27 x 0,25 | 3,10 | 23,0 | 14,4 |
6610250 | 2,50 | 50 x 0,25 | 3,70 | 35,0 | 24,0 |
6610400 | 4,00 | 56 x 0,30 | 4,30 | 51,0 | 38,0 |
6610600 | 6,00 | 84 x 0,30 | 4,80 | 71,0 | 58,0 |
6611000 | 10,00 | 80 x 0,40 | 6,30 | 125,0 | 96,0 |
6611600 | 16,00 | 128 x 0,40 | 8,80 | 195,0 | 154,0 |
6612500 | 25,00 | 196 x 0,40 | 10,00 | 300,0 | 240,0 |
6613500 | 35,00 | 276 x 0,40 | 11,40 | 410,0 | 336,0 |
▲ | compare |
Construction / data
Conductor
- bare stranded copper wire
Core-Ø
Core insulation
- PVC acc. to VDE 0207
Dimension
Technical characteristics
Temperature range
- static: -30 °C to +70 °C
- dynamic: -5 °C to +70 °C
Bending radius static
- > 10 x O.D.
Bending radius dynamic
- > 15 x O.D.
Operating voltage U₀
- 450 V
Operating voltage U
- 750 V
Testing voltage
- 2.500 V
Packaging
Rings at 100mLower and upper lengths according to availability. Special packaging on request.
Add-on information
PVC powerlines are acc. to the VDE directives