2-PURtronic-C-UL twisted pair (TP) Style 21223 - 10492 shielded, halogen-free, flame retardant
  • installation
  • mobile
  • halogen free
  • FRNC
  • outdoor
  • RoHS
  • REACH
  • CE

2-PURtronic-C-UL twisted pair (TP) 4x2xAWG28

Style 21223 - 10492 shielded, halogen-free, flame retardant
Order-No. 217082800

Application / Description

Twisted pair control cable for measuring-, signal, control-, and regulation technology and in locations subject to mechanical stress (external wiring) for indoor and outdoor use. The used PUR jacket material is exellent steady against hydrolysis, low temperature, microorganism as well as oil-resitant acc. to DIN EN 60811-2-1. Furthermore the PUR-jacket is very steady against grease, oxygen, ozone and feature a high stability in abrasion- and tensile strength. The wire is halogenfree acc. to IEC 60754-2.

Variant data

O.D.

  • approx. 6,40 mm

weight

  • 48,4 kg/km

Cu-weigth

  • 21,1 kg/km

skinning tool (jacket)

  • 40025

skinning tool (core)

  • 20300

Construction / data

Conductor

  • tinned stranded copper wire

Structure of conductor

  • 10 x 0,10 mm

Core-Ø

  • approx. 1,05 mm

Core insulation

  • PP - 9Y

Colour sequence

Pre-twisting

  • conductors to pairs

Twisting

  • pairs in layers, foil taping

Taping

  • foil taping

Overall shield

  • tinned copper braid, approx. 85% coverage, drain wire

Outer jacket

  • PUR - 11Y

Outer jacket colour

  • black sim. RAL 9005

Dimension

  • 4x2xAWG28

Technical characteristics

Flamm­ability

  • flame retardant acc. to IEC 60332- 1-2 and VW-1 (UL), FT-1 (cUL)

Temperature range

  • static: -50 °C to +80 °C
  • dynamic: -30 °C to +80 °C

Bending radius static

  • > 5 x O.D.

Bending radius dynamic

  • > 10 x O.D.

Operating capacity (C/C)

  • approx. 45 pF/m

Characteristic impedance

  • 110 Ohm +/- 15% @ 0,3 - 1,0 MHz

Operating voltage

  • 600 V

Testing voltage

  • 2.000 V

Insulation resistance

  • > 200 MOhm x km at + 20°C

Conductor resistance

  • max. 239,0 Ohm/km

Packaging

Rings at 100m, Reels at 500m
Lower and upper lengths according to availability. Special packaging on request.

Add-on information

jacket halogen-free and flame-retardant acc. to DIN VDE 0472 part 804 testing B/IEC 60332-1-2; oil-resistant acc. to DIN EN 60811-2-1, hydrolysis-resitant; low temperature flexible. The wire is halogen-free acc. to IEC 60754-2

Similar products