- installation
- mobile
- halogen free
- FRNC
- outdoor
- RoHS
- REACH
- CE
Application / Description
UL-twisted pair control cable, Style 21223/10492 (external wiring). The used PUR jacket material is exellent steady against hydrolysis, low temperature and microorganism. Furthermore the PUR-jacket is very steady against oils, grease, oxygen, ozone and feature a high stability in abrasion- and tensile strength. The wire is halogenfree acc. to IEC 60754-2.
Product range
Order-No. | Dimension | O.D. approx. mm | weight kg/km | Cu-weigth kg/km | skinning tool (core) | skinning tool (jacket) |
---|---|---|---|---|---|---|
217042800 | 2x2xAWG28 | 5,90 | 39,0 | 16,1 | 20300 | 40025 |
217082800 | 4x2xAWG28 | 6,40 | 48,4 | 21,1 | 20300 | 40025 |
217162800 | 8x2xAWG28 | 8,20 | 74,1 | 29,6 | 20300 | 40025 |
▲ | compare |
Construction / data
Conductor
- tinned stranded copper wire
Structure of conductor
- 10 x 0,10 mm
Core insulation
- UL-PP (Style 10492)
Colour sequence
Pre-twisting
- conductors to pairs
Twisting
- pairs in layers, foil taping
Taping
- foil taping
Overall shield
- tinned copper braid, approx. 85% coverage, drain wire
Outer jacket
- PUR, halogen-free, flame-retardant, (UL Style 21223)
Outer jacket colour
- black sim. RAL 9005
Technical characteristics
Temperature range
- static: -50 °C to +80 °C
- dynamic: -30 °C to +80 °C
Bending radius static
- > 5 x O.D.
Bending radius dynamic
- > 10 x O.D.
Operating capacity (C/C)
- approx. 45 pF/m
Characteristic impedance
- 110 Ohm +/- 15% @ 0,3 - 1,0 MHz
Operating voltage
- 600 V
Testing voltage
- 3.000 V
Insulation resistance
- > 200 MOhm x km at + 20°C
Conductor resistance
- max. 239,0 Ohm/km
Packaging
Rings, ReelsAdd-on information
jacket halogen-free and flame-retardant acc. to DIN VDE 0472 part 804 testing B/IEC 60332-1-2; oil-resistant acc. to DIN EN 60811-2-1, hydrolysis-resitant; low temperature flexible. The wire is halogen-free acc. to IEC 60754-2